Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T11CM00657
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/12/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/09/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) PLANS NEED REVISION FOR LOADS ON PANELS-NOT INSTALLED PER PLANS 2) USE APPROVED ARC SHIELDS-METALIC NOT APPROVED |
|
| 09/07/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FINISH PENDANT LIGHTING 2) SPLICES TO BE FOR WET LOCATION 3) BOXES OVER FILLED 4) PANEL DIRECTORY TO BE PER 408.4, ALSO NOT PER PLANS. WHERE ARE ALL CIRCIUITS ON PLANS ? 5) BOXES MORE 1/4" 314.20 6) NEED TO SEE BIC MACHINE TO VERIFY LISTING OR LETTER STATING WILL BE LISTED FOR FUTURE USE 7) EGRESS LIGHTING EXISTING 8) CIRCUIT FOR FRUIT FREEZER IS NOT CODE COMPLIANT AT TIME OF INSTALL 9) MAINTAIN WORKING SPACE IN FRONT OF PANELS 110.26 |
|
| 09/06/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PLEASE HAVE ALL PREVIOUS WRITE UPS ON SITE 2) VERIFY BOX FILL 3) VDV CABLING TO BE PER 725.3 & 8, 800.0 & 24 AND 300.11 4) PLEASE PROVIDE A LADDER TO INSPECT ABOVE CEILING SINCE TILE HAS BEEN INSTALLED 5) NEED CITY APPROVED SET OF PLANS ON SITE 6) PLEASE HAVE ELECTRICIAN PRESENT TO ANSWER QUESTIONS |