Permit: T11CM00643

Parcel: 13317064C

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
07/25/2011 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
1) LEAVE OUT A TILE AT EACH UNIT FOR FINAL INSPECTION
07/15/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) EXTEND VENTS IN CONDENSATE TRAPS ABOVE DRAIN PANS
2) WHERE ARE THE SECONDARY DRAINS ?
3) OPEN FRESH AIR DAMPERS
4) HP3 NEEDS ACCESS PANEL
5) NEED SMOKE DETECTORS
6) OK TILES ROOMS 117 THRU 123, CORRIDOR #125, 126 THRU 129, 163 THRU 155 AND 142 THRU 150
05/26/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) CONDENSATE LINES OK TO INSULATE AND COVER IN WALL
2) SUPPLY AND EXHAUST IN HARD LIDS OK