Permit: T11CM00636

Parcel: 12217365A

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
07/13/2011 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
05/04/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :* 1) NOTE: WIRE GOING THROUGH MIDDLE 1/3 OF RAFTER
OK WALL & LIDS PORCH AREA
04/27/2011 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROTECT NM CABLES LESS THAN 1 1/4" 300.4
2) STRAP VDV CABLING 725.8
3) SECURE NM CABLE WITHIN 12" OR 8" OF BOXES 312.5
4) CEILING BOX TO BE FAN RATED
5) NEED REVISED PLANS FOR ELECTRIC - WILL NEED CITY STAMP