Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/09/2011 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 04/22/2011 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 03/28/2011 | MECHANICAL - INTERMEDIATE | Partial Approval | 1) PROVIDE DAMPERS AT O.S.A. 2) PROVIDE INSTALL INSTRUCTIONS ON V.A.V. UNITS FOR INLET STRAIGHT LENGTH 3) CONTROL DAMPERS AT R/A INLETS AT FAN COILS 4) REMOVE COMBUSTIBLES FROM PLENUM CEILING 5) OK TO INSTALL FLEX AND REGISTERS |
|
| 03/15/2011 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* |