Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/05/2011 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 03/28/2011 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) COMBO STARTER/DISCONNECTS ON AH UNITS DO NOT MEET WORKING CLEARANCE REQUIREMENTS 110.26 NEC 2) PLANS CALL FOR 125 AMP PANEL 'NH' FIELD INSTALED 200 AMP-NEED ENGINEER OF RECORD TO OK OR ADDRESS, ALSO 125 CKT BREAKER TO FEED PANEL. PLEASE ADDRESS ROOF MTD CONDUIT AND WIRE FOR ADJUSTMENT FACTOR DUT TO HEAT PER 310.15 NEC |