Permit: T11CM00618

Parcel: 119215980

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T11CM00618

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
04/04/2011 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
03/29/2011 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ALL PVC JOINTS TO HAVE PRIMER, ALL PRIMER TO BE PURPLE IN COLOR PER U.P.C., PRIMER IS TO BE APPLIED PRIOR TO GLUE AND FITTING OF JOINT
2) PROVIDE P-TRAPS IN CONDENSATE LINES, VENT TO BE OUTSIDE CABINET
3) PROVIDE GRUMMETS AT ALL CABINET PENETRATIONS
4) PROVIDE SECONDARY DRAINS
5) REFRIDGERATION INSULATION TO CONTINUE OVER DRAIN PAN
6) PROVIDE FULL RADIUS AT FLEX DUCT BENDS, USE ELBOWS AS NEEDED