Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/04/2011 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 03/29/2011 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ALL PVC JOINTS TO HAVE PRIMER, ALL PRIMER TO BE PURPLE IN COLOR PER U.P.C., PRIMER IS TO BE APPLIED PRIOR TO GLUE AND FITTING OF JOINT 2) PROVIDE P-TRAPS IN CONDENSATE LINES, VENT TO BE OUTSIDE CABINET 3) PROVIDE GRUMMETS AT ALL CABINET PENETRATIONS 4) PROVIDE SECONDARY DRAINS 5) REFRIDGERATION INSULATION TO CONTINUE OVER DRAIN PAN 6) PROVIDE FULL RADIUS AT FLEX DUCT BENDS, USE ELBOWS AS NEEDED |