Permit: T11CM00601

Parcel: 122070550


Addresses:

4407 E LINDEN ST

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
03/29/2011 ELECTRIC - INTERMEDIATE Approved
03/02/2011 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED GROUND RODS AT SERVICE PANEL AND GROUNDED TO PANEL-PANEL NEEDS TO BE COMPLETED AND SAFE TO ENERGIZE
2) NEED TEMP RECEPTS AND GFI'S
3) NEED DRYWALL REMOVED FOR INSPECTION OR PROVIDE LETTER FROM ELECTRICAL CONTRACTOR ON LETTER ALL ELECTRIC IS SAFE AND MEETS MINIMUM CODE REQUIREMENTS
4) ALL ELECTRIC NEEDS TO BE DONE TO CODE
5) ALSO NOTICED SEVERAL PLUMBING VIOLATIONS