Permit: T11CM00571

Parcel: 124040010


Addresses:

1448 E 1ST ST


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T11CM00571

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
04/06/2011 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
03/21/2011 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MAINTAIN WORKING CLEARANCES FOR DISCONNECTING MEANS
2) TIGHTEN LOOSE FITTINGS
3) WILL NEED PANEL REVISIONS FOR CIRCUITS AND PANELS
4) PROTECT VDV CABLES (T-STAT) FROM SHARP METAL EDGES AND FOR PHYSICAL PROTECTION 725
5) NO MORE THAN 360 DEGREE IN CONDUIT RUNS
6) VERIFY ACCESSIBILITY 440.14
7) VERIFY POINT OF ORIGIN FOR DEMO