Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T11CM00571
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/06/2011 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
03/21/2011 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MAINTAIN WORKING CLEARANCES FOR DISCONNECTING MEANS 2) TIGHTEN LOOSE FITTINGS 3) WILL NEED PANEL REVISIONS FOR CIRCUITS AND PANELS 4) PROTECT VDV CABLES (T-STAT) FROM SHARP METAL EDGES AND FOR PHYSICAL PROTECTION 725 5) NO MORE THAN 360 DEGREE IN CONDUIT RUNS 6) VERIFY ACCESSIBILITY 440.14 7) VERIFY POINT OF ORIGIN FOR DEMO |