Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T11CM00541
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/07/2011 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
03/17/2011 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
03/11/2011 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GROUNDING ELECTRODE TO BE STRAPPED TO WALL 2) PANEL BREAKER LABLED BACK FEED ON LINE AND LOAD 3) LOW VOLTAGE WIRES MISSING PLASTIC BUSHINGS ON END OF EMT PIPE 4) GFI TO BE MOUNTED TO WALL 5) LADDER TO LOOK AT ROOF SOLAR PANELS 6) GARAGE TO BE OPENED TO INSPECT INVERTER |