Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/22/2011 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 03/17/2011 | ELECTRIC - RECONNECT | Not ready for Inspection | IVRS - Inspection :* 1) GATES LOCKED |
|
| 03/07/2011 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PANEL HAS BEEN INCREASED FROM 60 AMP TO 125 AMP. ADD INCREASE TO PERMIT 2) NEW PANEL REQUIRES GROUND ROD SYSTEM OR VERIFY EXISTING GROUND 3) 30 AMP DRYER CIRCUIT WIRING UNDERSIZED 4) REMOVE ALL EXTERIOR ROMEX NOT TO CODE THROUGHOUT 5) WHITE HOT LEADS IN PANEL MUST BE BLACK OR RED TAPE OK 6) CONDENSATE MAY NOT RELEASE INTO VENT PIPE. TERMINATE TO ROOFS EDGE. MISSING REQUIRED 110 GFCI SERVICE OUTLET 8) 2 WIRE OUTLETS 2 AND 2 WIRE WITH GROUND MIXED THROUGHOUT. RESTORE TO ORIGINAL STATE OR GFCI PROTECT 9) CONTACT TEP ON CONNECTION TO 3/4" RISER MINIMUM 2" REQUIRED |
|
| 03/04/2011 | ELECTRIC - RECONNECT | Not ready for Inspection | IVRS - Inspection :* 1) PANEL REPLACED WITH INTERIOR SUB PANEL NOT FOR EXTERIOR USE 2) NEW PANEL NOT GROUNED 3) SECURE DISCONNECTTO WALL 4) NEXT DENIAL MAY RESULT IN REFEE 5) HAVE QUALIFIED ELECTRICIAN PERFORM WORK 6) STOPPED INSPECTION |
|
| 03/02/2011 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WIRES FROM METER TO PANEL TO BE REPLACED 2) MAIN BREAKER HAS 2 WIRES ON 1 LUG 3) PIGGY BACK BREAKER HAS 2 WIRES ON 1 LUG 4) BREAKER BLANKS MISSING 5) TO LEFT OF PANEL 20 AMP BREAKER 2 POLE TO BE IN 3R ENCLOSURE 6) CIRCUIT TO A/C TO BE PHASED NEUTRAL IN PANEL AND AT A/C DISCONNECT 7) A/C FUSES TO BE 45A NOT 60-AMPS 8) GFI'S IN KITCHEN MISSING BOX EXTENSION OR ARCH SHIELDS |
|
| 02/23/2011 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED LADDER TO ACCESS ROOF TO INSPECT NEW UNIT 2) NEED TO STRAP ? TO WALL FOR NEW A/C CIRCUIT 3) NEED TO DISCONNECT EXTENSION CORD AT MAIN PANEL 4) NEED GFCI PROTECTION ON ALL KITCHEN/BATH COUNTER RECEPT 5) NEED SMOKE DETECTORS IN ALL BEDROOMS AND HALLWAYS 6) ELECTRICAL NEEDS TO BE SAFE TO RELEASE |