Permit: T11CM00508

Parcel: 136390680


Addresses:

4702 S LANTANA CI

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
03/24/2011 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
03/23/2011 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
DENIED- PROVIDE A 15LB PRESSURE GAUGE, PROVIDE THE ROOFTOP DRAWING.
03/04/2011 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE A PRESSURE TEST ON ALL GAS PIPING TO UNIT ON ROOF
2) FITTINGS ARE TO NUMEROUS FOR A SOAP TEST
3) PROVIDE THE REQUIRED STRUCTURAL DRAWING FOR A NEW A/C ON THE ROOF
4) I.D. THE CIRCUIT BREAKER FOR THE SERVICE RECEPT, MUST NOT EXCEED 20 AMP
02/28/2011 MECHANICAL - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*