Date Description Inspector Results Comments
07/28/2011 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
1) COMPLETE SHUTTERS IN FRONT
2) SEAL CONDUITS IN WALK INS
3) CALL FOR FINAL WHEN READY
4) OK TCO (ELECTRIC) TO TEST EQUIPMENT
07/14/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*

OK 3 POLE BSES
OK FOR SIGN BASES
06/09/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) NORTH SIDE OK 24" AND NORTH EAST SIDE TO LIGHT POLE 24" EAST SIDE 18" UNDER SIDE WALK AND 24" PLUS UNDER PAVEMENT
06/08/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) PARKING LOT TO BE PER 300.5 24" OTHER AREAS 18"
2) PARTIAL OK WEST OF BLDG
05/11/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) OK SECONDARYS TO BLDG FROM X FORMER AND PHONE. 3/4 STUB OUT LTG AND DRIVE THRU
3) OK GROUND RODS AND TEMP SERVICE WILL EPRMIT SEPERATELY