Permit: T11CM00490

Parcel: 121122600


Addresses:

1518 N BEVERLY AV

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
11/28/2012 BUILDING - FINAL Approved IVRS - Inspection :*
11/23/2012 BUILDING - FINAL Partial Approval DISCONNECT NOT FUSED CORRECTLY PROVIDE CONNECTORS FOR ROMEX CONNECTIONS AT FIXTURES, PAINT EXPOSED PVC W/LATEX PAINT AND SUPPORT EVERY 4'.
PROVIDE MIN. 2" R8 DUCT LINER IN EXPOSED DUCT ON ROOF. SECURE THE ANGLE IRON STAND TO ROOF.