Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/24/2012 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 02/23/2012 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FLEX TERMINATION FOR WALL LIGHT (EAST) NOT TERMINATED, ALSO OTHER VARIOUS FLEX TERMINATIONS NOT SEATED IN CONNECTORS CORRECTLY DUE TO ROUGH AND UNEVEN FLEX CUT ENDS-110.3 & 110.12 NEC |
|
| 02/21/2012 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CALLED AND LEFT MSG. WITH ETA PER REQUEST 2) CONTRACTOR NOT ON SITE, NO RETURN MSG. 3) AREA FENCED 4) RESCHEDULE INSPECTION |
|
| 02/16/2012 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) SECURE FLEX CONDUIT PER 248.30 20 MISSING PLASTER RINGS 3) TIGHTEN LOOSE FITTINGS 4) WHITE CONDUCTORS IN RACEWAYS-NOT ALLOWED TO BE TAPED FOR MARKING 5) FINISH MAKE UP 6) JUNCTION BOX TO BE ACCESSIBLE 7) USE COLORS PER CITY AMENDMENTS 310.5 8) FILL UNUSED OPENINGS IN BOXES 9) CEILING FAN NOT ON PLANS AND SWITCH 10) VERIFY BOX FILL |