Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/17/2011 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 03/15/2011 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BOND BUSHINGS MISSING ON SOLAR PANEL DISCONNECT AND J-BOX AND CHECK FITTINGS 2) STRAPPING MISSING ON SOLAR STANDS 3) BONDING MISSING AT SERVICE 4) NEUTRAL TO BE REMOVED AT SOLAR PANELS 5) LABEL MISSING ON SERVICE |