Permit: T11CM00447

Parcel: 11446206B

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T11CM00447

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/29/2011 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) AIR BALANCE OK
2) LETTER FROM ENGINEER OK
03/17/2011 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
03/11/2011 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) STEP UP CONDENSATE TO 1" AFTER 1ST TEE
2) USE PURPLE PRIMER ON ALL PVC FITTINGS PRIOR TO GLUE
3) PAINT EXPOSED PVC WITH LATEX PAINT
4) SUPPORT PVC EVERY 4'
5) TERMINATE TO WITHIN 6" OF THE GROUND
6) CAP OFF VENTS
7) PERMANENTLY I.D. UNITS ON ROOF
8) AT LEAST 1 DISCONNECT WIRED BACKWARDS-CHECK ALL
9) NEED TO SEE ABOVE CEILING DUCTING
10) SCHEDULE BLDG AND ELECTRIC INSPECTIONS
11) PROVIDE AIR BALANCE REPORT FOR FINAL
12) PROVIDE A LETTER FROM ENGINEER IF CHANGING ANYTHING ON PLANS
13) 11 PSI TEST IS OK