Permit: T11CM00423

Parcel: 12803078A


Addresses:

5628 E BROADWAY BL


Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T11CM00423

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/01/2011 FIRE - FINAL Approved
11/30/2011 FIRE - FINAL Denied 1. The sign "This Door IS Blocked" must be secured to the rear door. Sign 0.75 inch wide and 6 inch high.
11/22/2011 FIRE - FINAL Denied Front cover sheet T1.0 states "Building Fully Sprinkered" when it's not. Need to remove or sprinkler building.
Again on sheet T1.0 under responsibility schedule states alarm to be installed, remove from sheet or install alarm.
Rear door welded shut needs to be label with the following wording "THIS DOOR BLOCKED" stroke 0.75 inch wide and 6 inch high lettering on a contrasting background. Any door that egresses to the outside shall be label with the above wording when said door is made inaccessible (on pg. D1.0).
11/08/2011 FIRE - FINAL Denied 1. Rear exit 'E' side cannot be blocked.
2. Remove all drop down bars.
3. Thumb turn on front 'E' door. Remove key lock.
4. Means of egress illumination required on 'E' end of building (new section).
10/31/2011 FIRE - FINAL Denied No approved plans on site.