Permit: T11CM00420

Parcel: 99999999C

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/15/2011 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/12/2011 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) USE A MORE PERMANENT WARNING LABEL FOR SERVICE DISCONNECT, THE OTHER ONE FELL OFF
12/08/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED WORK SPACE AT DISCONNECTING MEANS 110.26 (0-150V)
2) PROTECT CONDUCTOR 352.46 AND 300.4
3) NEED MARKING LABELS PER 692.53, 54 & 56
4) PLAND TO BE ON SITE
12/02/2011 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*