Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/04/2011 | PLUMBING - FINAL | Approved | PER INSP CARD | |
| 09/08/2011 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ABS AND PVC ARE NOT PERMITTED TO BE INSTALLED IN EXPOSED EXTERIOR LOCATIONS 2) HOW IS THE WATER SUPPLY TO THE DISPENSOR PROTECTED ? 3) ARMAFLEX INSULATION DETERIORATED IN U.V. LOCATIONS, USE ROOFING MASTIC (WHITE) TO WEATHER PROOF INSULATION 4) PROVIDE LISTING FOR AAV TO BE INSTALLED IN EXPOSED EXTERIOR LOCATION |
|
| 08/24/2011 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* WAITING ON DATER DISPENSOR INSTALL ONLY |
|
| 08/22/2011 | PLUMBING - FINAL | Not ready for Inspection | PROVIDE BACTERIA REPORT, STERILIZATION REPORT ON SITE. PROVIDE LONG RADIUS 90 DEG AT SINK AT VACUUM STATION WITH PLASTIC MALG ADAPTER. ALL (1) TYPE MATERIAL. INSULATE HOSE BIB EXPOSED TO GREEZING. PROVIDE ALL PVC AT AIR ADMITTANCE VALVE AT WATER STATION. COMPLETE WATER STATION INSTALLATION |
|
| 08/16/2011 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* |