Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY SERVICE
Permit Number - T11CM00419
Inspection Description - ELECTRIC - TEMPORARY SERVICE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/22/2011 | ELECTRIC - TEMPORARY SERVICE | Approved | IVRS - Inspection :* | |
| 08/19/2011 | ELECTRIC - TEMPORARY SERVICE | Not ready for Inspection | IVRS - Inspection :* | |
| 08/18/2011 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) BOND JUMPERS ON SUPPLY SIDE 2/0 CU. PER 250.66 NEC 2) EQUIPMENT GROUNDS TO BE RUN IN EACH RACEWAY PER 250.122 F 3) POST BOND TEMP POWER FOR TEST |
|
| 08/17/2011 | ELECTRIC - TEMPORARY SERVICE | Not ready for Inspection | IVRS - Inspection :* 1) POST BOND FOR TEMP POWER FOR TEST 2) COMPLETE TERMINATIONS AT SES |
|
| 08/16/2011 | ELECTRIC - TEMPORARY SERVICE | Not ready for Inspection | IVRS - Inspection :* | |
| 05/10/2011 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SEE NOTES LAST INSPECTION |
|
| 05/06/2011 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PERMIT REQUIRED FOR TEMP SERVICE ON MODULAR OFFICE TRAILER |