Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Date Description Inspector Results Comments
08/08/2011 FIRE SPKLR - FINAL Approved
08/01/2011 FIRE SPKLR - FINAL Not ready for Inspection 1. 4 sprinkler heads greater then 7 ft 6 in off wall.
2. 1 sprinkler head closer then 4 inches to wall.
07/13/2011 FIRE SPKLR - FINAL Not ready for Inspection 1. Remove painted heads x2 in office space area.
2. Sprinkler head in production room #1 on south wall needs to be four inches from wall.
3. Sprinkler heads in production room #1 north lights heads need to be raised.
4. Sprinkler head needs to be dropped down through ceiling in small confrence room.