Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
Permit Number - T11CM00408
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/08/2011 | FIRE SPKLR - FINAL | Approved | ||
08/01/2011 | FIRE SPKLR - FINAL | Not ready for Inspection | 1. 4 sprinkler heads greater then 7 ft 6 in off wall. 2. 1 sprinkler head closer then 4 inches to wall. |
|
07/13/2011 | FIRE SPKLR - FINAL | Not ready for Inspection | 1. Remove painted heads x2 in office space area. 2. Sprinkler head in production room #1 on south wall needs to be four inches from wall. 3. Sprinkler heads in production room #1 north lights heads need to be raised. 4. Sprinkler head needs to be dropped down through ceiling in small confrence room. |