Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T11CM00408

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
08/09/2011 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
06/21/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK WALLS 102, 110-114 SUBJECT TO LETTER
06/14/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) PLANS CALL FOR 3/4" MINIMUM CONDUIT-NEED LETTER FROM ENGINEER AUTHORIZING USE OF M/C CABLE
2) PROTECT FLEX AT SHALLOWS OF STUDS
3) PLANS CALL FOR CONDUIT NOT PVC ABOVE GRADE
4) OK WALLS 100, 101, 103, 106, 108, 109, 105, 116 AND SERVER SUBJECT TO LETTER FOR M/C
5) OK POUR 2 3/4" PVC STUDS