Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/06/2012 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 01/31/2012 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) PROVIDE A PROTECTIVE COATING ON ALL EXPOSED ARMA FLEX ON ROOF 2) PERMANENTLY I.D. ALL EQUIPMENT ON ROOF-NO INK 3) PROVIDE AIR BALANCE REPORT AND DUCT SMOKE DETECTOR TEST |