Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/10/2011 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 06/07/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK ELECTRIC ABOVE CEILING |
|
| 06/06/2011 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 06/03/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) SUPPORT FLEX INSIDE HOOD 12" 2) FILL UNUSED OPENINGS IN PANEL RACEWAYS 3) CORRECTLY IDENTIFY SHUT TRIP NEUTRALS 200.6 4) CLEAN SURFACE UNDERGROUND BAR LIGHTING GUTTER 250.12 5) SUPPORT AND PROTECT VDV CABLING 725.8 6) OK TO CLEAR TMPP SUBJECT TO BOND |