Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/24/2011 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 03/22/2011 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) VERTICAL PIPING TO BE SUPPORTED 2) OVER HEAD PIPING TO BE SUPPORTED 3) BACK PITCHED SECTIONS TO BE CORRECTED 4) HOW ARE YOU PROTECTING THE ABS FROM THE SHARP EDGES OF THE METAL STUD ? |
|
| 03/17/2011 | PLUMBING - INTERMEDIATE | Partial Approval | BACKING AT MS, CARRIES FOR URINAL,SLOPE ON URINAL DRAIN ARM, HARD CAP INLET ON COSET CARRIER.ADD SUPPORTS TO ABS.SAFETY PLATES. |