Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/02/2011 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 10/28/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) INSTALL BONDING BUSHINGS OVER 250 VOLTS WHERE USING RE-WASHERS, INSUL. BUSHINGS AT TERMINATIONS WHERE #4 OR LARGER CONDUCTORS 2) LABELS PER 690.17 SEE PLAN E3.3 3) GEC PER E3.2 690 NEC |