Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/31/2011 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) HAVE AIR BALANCE REPORT FOR BLDG INSPECTOR 2) EVERYTHING ELSE OK FOR MECH. |
|
| 05/26/2011 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) OUTSIDE AIR DAMPERS HAVE BEEN MANUALLY OPENED TO EXCEED MINIMUM REQUIREMENTS, SUPPLY AIR TO RESTROOMS CLOSED TO MAINTAIN NEGATIVE PRESSURE IN THOSE AREAS 2) HOOD SYSTEM NOT BALANCED UNABLE TO CONTAIN SMOKE, NO COOKING IS TO OCCUR, SEE BLDG INSPECTOR FOR TEMP C OF O FOR STOCKING AND EQUIPMENT SET UP ONLY |