Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - PROGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/25/2011 | MECHANICAL - PROGRESS | Approved | IVRS - Inspection :* 1) PERMANENTLY I.D. EQUIPMENT ON ROOF 2) PROVIDE A PROTECTIVE COATING ON ALL EXPOSED ARMAFLEX 3) PROVIDE FUSES IN ELECTRIC DISCONNECTS FOR CONDENSORS 4) PROVIDE AIR BALANCE REPORT 5) NEED CAPTURE, CONTAINMENT AND HEAT SENSOR TEST |