Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - HOODS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/31/2011 | MECHANICAL - HOODS | Approved | IVRS - Inspection :* | |
| 05/18/2011 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1) FIRE WRAP ON CLEANOUTS TO BE INSTALLED PER INTSTALL INSTRUCTIONS |
|
| 05/17/2011 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1) 1ST LAYER FIRE WRAP OK, OK FOR 2ND LAYER |
|
| 05/16/2011 | MECHANICAL - HOODS | Not ready for Inspection | IVRS - Inspection :* 1) LARGE HOOD 1ST LAYER JOINTS NOT PROPERLY FITTED 2) SMALL HOOD SECOND LAYER INSTALLED WITHOUT DUCT CLEANOUT |
|
| 05/13/2011 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :*1) 1ST LAYER ON 4' HOOD OK 2) SMOKE/LEAK TEST ON DOUBLE HOOD OK |
|
| 05/12/2011 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1) DUCT SMOKE/LEAK TEST ON 4' HOOD OK-OK 1ST LAYER WRAP |