Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T11CM00340
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/07/2011 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 02/11/2011 | PLUMBING - FINAL | Denied | 1. ALL POTABLE PIPING ON THE ROOF TO BE PROPERLY INSULATED AND PROTECTED FROM SUN UV EXPOSURE. 2. COMPLETE AND SEAL ALL POTABLE INSULATION IN ENCLOSURE. (WATER HEATER AREA) PROPERLY. 3. PROVIDE LISTING FOR THE PAD USED FOR MINIMUM 900 PLUS POUNDS. 4. PROVIDE CORRECT COMBUSTION AIR FOR GAS WATER HEATER AT NEW LOCATION. 5. PROVIDE A MEANS TO TEST THE NEW GAS PIPING. 6. GAS FLEX CANNOT PENETRATE ENCLOSURE. 7. SINGLE WALL VENT REQUIRES MINIMUM SIX INCHES CLEARANCE FROM COMBUSTIBLES. 8. ENCLOSURE DOES NOT PROVIDE SPACE TO REMOVE BOTH HEATER AND STORAGE TANK. 9. PROVIDE DEDICATED OUTLET OR GFCI PROTECTED OUTLET FOR PUMP SYSTEM. 10. GAS PIPING CANNOT BLOCK OUTLET, CORD CANNOT BE PINCHED BY THE ENCLOSURE. 11. PROVIDE FASTENERS ON VENT CONNECTOR. 12. WEATHER PROOF ELECTRICAL BOX TO BE CLOSEABLE AND WEATHER TIGHT. 13. TEE CONNECTION TO EXISTING COLD IS READY TO LEAK, AND IS DEFECTIVE. MAY NOT BE A COMPLETE LIST. |