Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T11CM00330
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/27/2011 | MECHANICAL - FINAL | Approved | PER INSP COPY | |
04/22/2011 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
04/21/2011 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) CONDENSATE TRAP BACKWARDS ON A/C 2) MARK UNIT DATA PLATES WITH PROPER HEAT STRIPS AND FUSE ACCORDINGLY 3) PERMANENTLY I.D. UNITS 4) PROVIDE AIR BALANCE REPORT 5) PROGREAM T-STATS FOR A/C FANS TO RUN CONTINOUSLY DURING OCCUPIED HOURS 6) INTERLOCK EXHAUST FANS PER MECHANICAL NOTES |