Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T11CM00329

Parcel: 121016460


Addresses:

1951 N WILMOT RD 01

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
04/27/2011 MECHANICAL - FINAL Approved PER INSP COPY
04/22/2011 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
04/21/2011 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) CONDENSATE TRAPS BACKWARDS
2) MARK UNIT DATA PLATE WITH PROPER HEAT STRIP AND FUSE ACCORDINGLY
3) PERMANENTLY I.D. UNIT
4) PROVIDE AIR BALANCE REPORT
5) INTERLOCK EXHAUST FANS AS PER MECHANICAL NOTES
6) PROGRAM T-STATS FOR A/C FAN TO RUN CONTINOUSLY DURING OCCUPIED HOURS