Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T11CM00326
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/25/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/24/2011 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) RECALL INSPECTION-CONTRACTOR ON SITE AND LEAVE PHONE NUMBER OF CONTACT PERSON 2) NO COMPLIANCE NOTE #3 AND #4 ? |
|
| 05/17/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The fixtures are not per plans and specifications.| 250* 1) NO WORK PROGRESS 2) A REFEE MAYBE ASSESED |
|
| 05/04/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WATER HEATER NOT A CORD AND PLUG APPLIANCE 2) BOXES IN COMBUSTIBLES TO BE FLUSH 314.20 & 314.21 3) NEED DISCONNECT FOR FIXTURES 410.73 (G) 4) PROTECT CONDUCTOR FROM SHARP METAL EDGES 5) ROOF RECEPT COVER TO BE PER 406.8 |