Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/17/2011 | PLUMBING - ABOVE CEILING | Approved | IVRS - Inspection :* 1) TRAP AND TRAP ARM SHALL BE THE SAME SIZE 2) SWEEP REQUIRED ON HORIZONTAL CHANGE OF DIRECTION 3) 1/4" PER FOOT SLOPE MINIMUM ON WASTE AND MAX ON TRAP ARM |
|
| 02/10/2011 | PLUMBING - ABOVE CEILING | Not ready for Inspection | 1. INSTALL SAFETY PLATES. SEAL PIPE INSULATION WITH ADHESIVE PER INSTALLATION INSRUCTIONS. SUPPORT THE PIPE NOT THE FITTINGS. SUPPORT PEX AT MAX. 32'. ISOLATE. | |
| 02/09/2011 | PLUMBING - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 02/08/2011 | PLUMBING - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* |