Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/20/2011 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 04/19/2011 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 03/30/2011 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) PROVIDE A ROOF JACK AT ELECTRIC CONDUIT THRU ROOF 2) EXTEND PVC DRAIN TO WITHIN 6" OF THE GROUND 3) SUPPORT MAX 4' AND USE REDWOOD OR PRESSURE TREATED 4) MARK THE UNIT DATA PLATE WHETHER THERE IS A HEAT STRIP OR NOT 5) SOME SECTIONS OF KD DUCT NOT SNAPPED TOGETHER AND CRIMPED END NOT INSTALLED INTO ELBOW PROPERLY |