Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T11CM00219
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/12/2012 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/11/2012 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) FINISH SEALS WALK IN 2) FINISH DIRECTORIES |
|
| 04/10/2012 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) PROTECT CONDUCTORS NORT END SECTION SES 2) PANEL DIRECTORIES TO BE PER 408.4 3) SEAL RACEWAYS WALK IN 300.7 4) EXIT LIGHTS NOT WORKING |
|
| 04/06/2012 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) BOXES MORE THAN 1/4" 314.20 2) RECEPT ON METAL COVERS 406.3 3) VERIFY LISTING AND LABELING-CREAMER,FROZEN BEVERAGE,TOP OVEN AND ? |
|
| 04/04/2012 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* ROOF: 1) MAINTAIN WORKING CLEARANCES AT DISCONNECTS 110.26 2) ISOLATE POWER INTERIOR OF A/C UNITS TO DISCONNECT BLDG: 1) SCREWS FOR MOUNTING TO BE APPROVED 2) USE CORRECT WIRE CONNECTORS FOR CONDUCTORS-POLES 3) MAINTAIN WORK CLEARANCES 110.26 4) OK AIR COMPRESS AND POWER WASHER UNIT |