Permit: T11CM00189

Parcel: 12510003F

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
03/04/2011 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
03/02/2011 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) PVC TO BE SUPPORTED AT EACH CHANGE OF DIRECTION OR ELEVATION, AND AT THE END OF BRANCHES-THEN REMOVE FOUR FEET BETWEEN HANGERS
2) LIKEWISE FOR COPPER EXCEPT 6' BETWEEN HANGERS MID STORY GUIDE FOR VERTICAL ABS
3) OK TO COVER WALLS TO ABOVE CEILING