Permit: T11CM00164

Parcel: 123110260


Addresses:

1028 E LESTER ST


Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T11CM00164

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
02/21/2013 PLUMBING - ROUGH, SOIL Approved
02/14/2013 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
02/06/2013 PLUMBING - ROUGH, SOIL Not ready for Inspection 1. Have licensed plumber on site at the time of the next inspection- Installation does not meet minimum requirements of any approved code.