Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/12/2011 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* 1) CORRECTIONS FROM 5/5/11 MADE OK 2) DON'T FORGET AT SINK: TRAP AND TRAP ARM TO BE THE SAME SIZE 3) CLOSET FLANGE OK 4) OK TO COVER WALLS S.T.O.I. |
|
| 05/06/2011 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 05/05/2011 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) ISOLATE ABS FROM METAL STUDS 2) SUPPORT PIPING PER TABLE 3-2 2006 UPC 3) PLAN CALLS FOR TYPE "L" COPPER 4) MINIMUM WASTE SIZE FOR A SINK IS 2" 5) HORIZONTAL X HORIZONTAL CHANGE OF DIRECTION TO BE A SWEEP |