Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T11CM00133
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/01/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
03/10/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INVERTER LB NIPPLES TO BE BONDED, WHERE ELECTRODE PASSES 2) FROM PANEL TO DISCONNECT TO METER PIPE STRAP AT DISCONNECT 3) PANEL SOLAR BREAKER TO BE 30A, LABEL BACK FEED HOT ON LINE AND LOAD 4) PIPE FROM INVERTER DISCONNECT TO ROOF TO BE STRAPPED 5) ON ROOF 1 WIRE PER LUG UNLESS LISTED FOR TWO OR MORE 6) PIPE FROM FIRST J-BOX COUPLING LOOSE STRUT TO BE DEEP 1 1/2 ON ROOF 7) FINISHING FOR SOLAR STRANDS MISSING 8) ATTIC IN GARAGE STRAP FLEX |