Permit: T11CM00133

Parcel: 133530840

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T11CM00133

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/01/2011 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/10/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INVERTER LB NIPPLES TO BE BONDED, WHERE ELECTRODE PASSES
2) FROM PANEL TO DISCONNECT TO METER PIPE STRAP AT DISCONNECT
3) PANEL SOLAR BREAKER TO BE 30A, LABEL BACK FEED HOT ON LINE AND LOAD
4) PIPE FROM INVERTER DISCONNECT TO ROOF TO BE STRAPPED
5) ON ROOF 1 WIRE PER LUG UNLESS LISTED FOR TWO OR MORE
6) PIPE FROM FIRST J-BOX COUPLING LOOSE STRUT TO BE DEEP 1 1/2 ON ROOF
7) FINISHING FOR SOLAR STRANDS MISSING
8) ATTIC IN GARAGE STRAP FLEX