Permit: T11CM00119

Parcel: 12405226B


Addresses:

924 E 6TH ST


Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T11CM00119

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/22/2011 FIRE - FINAL Approved
07/21/2011 FIRE - FINAL Denied Sprinkler head in hallway installed wrong, sidewall sprinkler head can not be more than 4" away from wall. Head at this time is 9" from wall.
FDC still not repaired hard to turn
Sprinkler permit under #T11BU00583
07/20/2011 FIRE - FINAL Denied Fix hangers for sprinkler piping in basement
Replace gauges on riser
Add sprinkler coverage in hallway
Replace painted head southeast entry door
Fix FDC hard to turn
Need inspector test valve
Replace painted signs on riser
07/18/2011 FIRE - FINAL Cancelled