Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T11CM00119
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/22/2011 | FIRE - FINAL | Approved | ||
07/21/2011 | FIRE - FINAL | Denied | Sprinkler head in hallway installed wrong, sidewall sprinkler head can not be more than 4" away from wall. Head at this time is 9" from wall. FDC still not repaired hard to turn Sprinkler permit under #T11BU00583 |
|
07/20/2011 | FIRE - FINAL | Denied | Fix hangers for sprinkler piping in basement Replace gauges on riser Add sprinkler coverage in hallway Replace painted head southeast entry door Fix FDC hard to turn Need inspector test valve Replace painted signs on riser |
|
07/18/2011 | FIRE - FINAL | Cancelled |