Permit: T11CM00119

Parcel: 12405226B


Addresses:

924 E 6TH ST


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T11CM00119

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
07/26/2011 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
07/12/2011 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
07/07/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) FINISH #2 PREVIOUS
07/06/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) NEED APPROVED GROUND ROD CLAMP FOR 1/0
2) SEPERATE GROUNDS AND NEUTRALS AT SUB PANELS
3) CLEAN DIRT AND FOREIGN MATERIAL FROM BOTTOM OF SUB PANELS
4) ONLY ONE CONDUCTOR PER LUG TERMINATION FOR NEUTRALS
5) ONLY ONE ALUMINUM CONDUCTOR PER LUG TERMINATION
07/01/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) DEVICES 8' AND DOWN TO BE INSTALLED OR PLATED
2) FINISH PANEL MAKE UP
3) 400 AMP SERVICE PLAN CALLS FOR 1/0 GROUNDING ELECTRODE CONDUCTOR
4) INSTALL 2ND BREAKER IN PANEL 'A' FOR 'B'
06/30/2011 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
WEST SERVICE:
1) UNCOVER GROUND RODS, WATER AND BONDS
2) PROTECT IN RACEWAYS SE CABLES
05/26/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
05/25/2011 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) CONTRACTOR WILL RESCHEDULE INSPECTION FOR R. HOLLANDER
05/23/2011 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) WIRING/CABLES MUST BE 1 1/4" BACK OF STUD OR FINISH WALL TO PREVENT DAMAGE FROM SCREWS OR NAILS PER 300 NEC
2) PLANS/PERMIT ?
05/19/2011 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE PHYSICAL PROTECTION FOR M/C CABLE IN SHALLOW GROVES
2) PROVIDE PHYSICAL PROTECTION FOR NM CABLE FROM SHARP METAL BOXES
3) PLEASE VERIFY PLASTER RING WITH BOXES-LARGE GAPS
4) SUPPORT NM CABLES WITHIN 12" OR 8" OF BOXES, ALSO AT EXHAUST FANS
5) PROTECT CONDUCTORS INSIDE BOXES 410.23
6) BLDG INSPECTOR TO VERIFY STRUCTUAL INTEGRITY OF JOIST IN ENTRY HALL
05/16/2011 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
05/10/2011 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED PROTECTION ON ALL ROMEX OR MAINTAIN 1 1/4" FROM STUD FACE
2) ELECTRICAL NEEDS TO BE COMPLETE FOR INSPECTIONS
3) PROVIDE APPROVED PLANS/PERMIT ON SITE FOR ALL INSPECTIONS