Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T11CM00119
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/26/2011 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
07/12/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
07/07/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) FINISH #2 PREVIOUS |
|
07/06/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) NEED APPROVED GROUND ROD CLAMP FOR 1/0 2) SEPERATE GROUNDS AND NEUTRALS AT SUB PANELS 3) CLEAN DIRT AND FOREIGN MATERIAL FROM BOTTOM OF SUB PANELS 4) ONLY ONE CONDUCTOR PER LUG TERMINATION FOR NEUTRALS 5) ONLY ONE ALUMINUM CONDUCTOR PER LUG TERMINATION |
|
07/01/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) DEVICES 8' AND DOWN TO BE INSTALLED OR PLATED 2) FINISH PANEL MAKE UP 3) 400 AMP SERVICE PLAN CALLS FOR 1/0 GROUNDING ELECTRODE CONDUCTOR 4) INSTALL 2ND BREAKER IN PANEL 'A' FOR 'B' |
|
06/30/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* WEST SERVICE: 1) UNCOVER GROUND RODS, WATER AND BONDS 2) PROTECT IN RACEWAYS SE CABLES |
|
05/26/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
05/25/2011 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) CONTRACTOR WILL RESCHEDULE INSPECTION FOR R. HOLLANDER |
|
05/23/2011 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) WIRING/CABLES MUST BE 1 1/4" BACK OF STUD OR FINISH WALL TO PREVENT DAMAGE FROM SCREWS OR NAILS PER 300 NEC 2) PLANS/PERMIT ? |
|
05/19/2011 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE PHYSICAL PROTECTION FOR M/C CABLE IN SHALLOW GROVES 2) PROVIDE PHYSICAL PROTECTION FOR NM CABLE FROM SHARP METAL BOXES 3) PLEASE VERIFY PLASTER RING WITH BOXES-LARGE GAPS 4) SUPPORT NM CABLES WITHIN 12" OR 8" OF BOXES, ALSO AT EXHAUST FANS 5) PROTECT CONDUCTORS INSIDE BOXES 410.23 6) BLDG INSPECTOR TO VERIFY STRUCTUAL INTEGRITY OF JOIST IN ENTRY HALL |
|
05/16/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
05/10/2011 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED PROTECTION ON ALL ROMEX OR MAINTAIN 1 1/4" FROM STUD FACE 2) ELECTRICAL NEEDS TO BE COMPLETE FOR INSPECTIONS 3) PROVIDE APPROVED PLANS/PERMIT ON SITE FOR ALL INSPECTIONS |