Permit: T11CM00119

Parcel: 12405226B


Addresses:

924 E 6TH ST


Inspection Status: Approved

Inspection History: ELECTRIC - UFER

Permit Number - T11CM00119

Inspection Description - ELECTRIC - UFER

Inspection Status - Approved

Date Description Inspector Results Comments
07/26/2011 ELECTRIC - UFER Approved IVRS - Inspection :*
07/20/2011 ELECTRIC - UFER Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) TIGHTEN FIXTURE TO BOX ON WALL
2) RANGE NEED ANTI TIP PER INSTRUCTIONS
3) BOXES MORE THAN 1/4" OR FLUSH IN COMBUSTIBLES 314.20
4) USE APPROVED HARD WARE WITH DEVICES NOT DRY WALL SCREWS
5) PROTECT BULB IN CLOSET AND INSTALL PER 410.8
6) ALL OUTLETS IN BEDROOMS (SMOKIES) TO BE ARC FAULT PROTECTION 210.12
7) MISSING FRONT PATIO EXTERIOR LIGHTS 210.70
8) PLEASE VERIFY OUTLET LOADS-NOT WIRED AS PER PLANS BEDS 1, 2 & 3
9) BED 3 WINDOW CHANGED TO DOOR-NO SWITCH AT EXIT TO CONTROL EXTERIOR LIGHT
10) WHERE IS RECEPT IN MECH ROOM ?
11) AT PANEL 'C' FILL UNUSED PORTION OF OPENINGS IN BACK OF PANEL WITH A NON COMBUSTIBLE PRODUCT
12) TIGHTEN LOOSE CONDUCTOR TERMINATIONS
13) FINISH OFFICE AND EXTERIOR
14) PARTIAL INSPECTION-ONLY SMALL STRUCTURE-GO THRU ENTIRE PROJECT TO COMPLETE
07/12/2011 ELECTRIC - UFER Not ready for Inspection IVRS - Inspection :*
1) BATHROOM LIGHT NOT INSTALLED, CEILING LIGHTS NOT INSTALLED, AIR HANDLERS NOT FINISHED, CELLAR/BASEMENT NOT FINISHED AND HOODS MISSING
2) NO POWER AT THIS TIME
05/26/2011 ELECTRIC - UFER Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) WALL IN BLDG OK
2) RICK TO COME INSPECT SERVICE