Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/04/2011 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 01/24/2011 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CONDENSATE CANNOT BE REDUCED FROM 3/4", CANNOT HAVE A FAUCET ON THE END, CANNOT RUN UP HILL AT ANY POINT, MUST BE SUPPORTED EVERY 4' AND PAINTED WITH LATEX PAINT. BE SURE TO USE PURPLE PRIMER ON ALL FITTINGS PRIOR TO GLUE 2) REPAIR LOW VOLTAGE CONDUIT AT ROOF JACK AND SEAL 3) ACCORDING TO THE WAY THE DATA PLATE WAS MARKED, YOU NEED TO SEPERATE CIRCUIT FOR THE HEAT STRIP 4) PROVIDE THE REQUIRED GFI SERVICE RECEPT ON THE ROOF |