Permit: T11CM00116

Parcel: 133412670


Addresses:

9120 E 9TH ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
02/04/2011 MECHANICAL - FINAL Approved IVRS - Inspection :*
01/24/2011 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CONDENSATE CANNOT BE REDUCED FROM 3/4", CANNOT HAVE A FAUCET ON THE END, CANNOT RUN UP HILL AT ANY POINT, MUST BE SUPPORTED EVERY 4' AND PAINTED WITH LATEX PAINT. BE SURE TO USE PURPLE PRIMER ON ALL FITTINGS PRIOR TO GLUE
2) REPAIR LOW VOLTAGE CONDUIT AT ROOF JACK AND SEAL
3) ACCORDING TO THE WAY THE DATA PLATE WAS MARKED, YOU NEED TO SEPERATE CIRCUIT FOR THE HEAT STRIP
4) PROVIDE THE REQUIRED GFI SERVICE RECEPT ON THE ROOF