Permit: T11CM00106

Parcel: 13602002L


Addresses:

8240 E 22ND ST #118


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T11CM00106

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/07/2012 MECHANICAL - FINAL Approved IVRS - Inspection :*
04/05/2012 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) ITEMS DATED 8/30/11-#1,2,3,4,5,6,7,8,9 AND 10 HAVE NOT BEEN CORRECTED
2) REPAIR BROKEN PVC CONDENSATE ON ROOF
3) PROVIDE OUTSIDE AIR FILTERS
4) PROVIDE AIR BALANCE REPORT
08/30/2011 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) PROVIDE FULL LENGTH SLEEPERS SPANNING ROOF JOISTS
2) PROVIDE ROOF JACKS AT ROOF PENETRATIONS
3) PROVIDE REDUCER WASHERS AT ELECTRIC CONNECTION TO A/C UNIT
4) DO NOT USE WHITE WIRE FOR A/C POWER
5) PROVIDE HOSE CLAMPS AT CONDENSATE CONNECTIONS TO NEW A/C
6) A/C UNIT OVERFUSED
7) PROVIDE FRESH AIR INTAKES
8) TERMINATE CONDENSATE TO AN APPROVED LOCATION
9) MARK DATA PLATE ON EXISTING A/C AND FUSE ACCORDINGLY
10) PAINT PVC ON ROOF WITH LATEX PAINT
11) SEE BLDG INSPECTOR FOR TCO