Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T11CM00106
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/07/2012 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
04/05/2012 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) ITEMS DATED 8/30/11-#1,2,3,4,5,6,7,8,9 AND 10 HAVE NOT BEEN CORRECTED 2) REPAIR BROKEN PVC CONDENSATE ON ROOF 3) PROVIDE OUTSIDE AIR FILTERS 4) PROVIDE AIR BALANCE REPORT |
|
08/30/2011 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) PROVIDE FULL LENGTH SLEEPERS SPANNING ROOF JOISTS 2) PROVIDE ROOF JACKS AT ROOF PENETRATIONS 3) PROVIDE REDUCER WASHERS AT ELECTRIC CONNECTION TO A/C UNIT 4) DO NOT USE WHITE WIRE FOR A/C POWER 5) PROVIDE HOSE CLAMPS AT CONDENSATE CONNECTIONS TO NEW A/C 6) A/C UNIT OVERFUSED 7) PROVIDE FRESH AIR INTAKES 8) TERMINATE CONDENSATE TO AN APPROVED LOCATION 9) MARK DATA PLATE ON EXISTING A/C AND FUSE ACCORDINGLY 10) PAINT PVC ON ROOF WITH LATEX PAINT 11) SEE BLDG INSPECTOR FOR TCO |