Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T11CM00106
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/21/2011 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* 1) ALL TESTING, CLOSET FLANGES AND INSULATION OK |
|
09/20/2011 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) PROVIDE DWV TEST ON ALL PIPING 2) PROVIDE FIXTURE FITTINGS FOR BACK TO BACK LAVS 3) COMPLETE SHOWER VENT 4) PROVIDE WATER VALVES PER PLAN ? 5) HOW DOES YOUR RESTROOM DIMENSION WORK ON THE EAST SIDE ? 6) HOW DOES SHOWER STALLS SCOPE TO DRAINS CORRECTLY ? 7) CLOSET FLANGES OK FOR FINISH CONCRETE, ? OR SHEET VINYL ONLY 2) PROVIDE FIXTURE CARRIERS PER PLAN OR STAMPED LETTER FROM ENGINEER DELETING THEM |
|
08/08/2011 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* |