Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T11CM00103
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/29/2011 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
08/03/2011 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE CONDENSATE FOR A/C UNITS 2) FIRE DAMPERS INSTALLED IN A CEILING NOT 1 HOUR RATED. WHY ? 3) INSULATE AND SEAL ALL SUPPLY & RETURN DUCTS 4) PROVIDE A FRESH AIR INTAKE ON NEW A/C UNITS 5) PROVIDE AIR BALANCE REPORT 6) PAINT ALL EXPOSED BLACK IRON 7) PROVIDE A HINGE ? AND GASKET AT EXHAUST FAN 8) PROVIDE GREASE RECEPTORS AT FANS 9) INTERLOCK MAKE UP AIR 10) PROVIDE SLEEPERS AT CONDENSOR 11) SERVICE RECEPTS REQUIRED ON ROOF 12) GET DIRECTION FROM ENGINEER ABOUT FIRE DAMPERS LOCATION |
|
08/02/2011 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSULATE ALL SUPPLY AND RETURN DUCTS TO BREAK ROOM/MANAGERS OFFICE 2) FIRE/SMOKE DAMPER NOT INSTALLED CORRECTLY-PROVIDE INSTALL INSTRUCTIONS 3) WHERE IS THE SMOKE DETECTOR ? 4) SEAL ALL JOINTS AND ELBOW GORES 5) WHERE IS THE CONDENSATE DRAIN ? 6) ITEMS TO NUMEROUS TO LIST 7) MECHANICAL CONTRACTOR TO BE ON SITE AT NEXT INSPECTION 3) PROVIDE INSTALL |