Permit: T11CM00103

Parcel: 12201024J


Addresses:

3920 E GRANT RD


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T11CM00103

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/29/2011 MECHANICAL - FINAL Approved IVRS - Inspection :*
08/03/2011 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE CONDENSATE FOR A/C UNITS
2) FIRE DAMPERS INSTALLED IN A CEILING NOT 1 HOUR RATED. WHY ?
3) INSULATE AND SEAL ALL SUPPLY & RETURN DUCTS
4) PROVIDE A FRESH AIR INTAKE ON NEW A/C UNITS
5) PROVIDE AIR BALANCE REPORT
6) PAINT ALL EXPOSED BLACK IRON
7) PROVIDE A HINGE ? AND GASKET AT EXHAUST FAN
8) PROVIDE GREASE RECEPTORS AT FANS
9) INTERLOCK MAKE UP AIR
10) PROVIDE SLEEPERS AT CONDENSOR
11) SERVICE RECEPTS REQUIRED ON ROOF
12) GET DIRECTION FROM ENGINEER ABOUT FIRE DAMPERS LOCATION
08/02/2011 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INSULATE ALL SUPPLY AND RETURN DUCTS TO BREAK ROOM/MANAGERS OFFICE
2) FIRE/SMOKE DAMPER NOT INSTALLED CORRECTLY-PROVIDE INSTALL INSTRUCTIONS
3) WHERE IS THE SMOKE DETECTOR ?
4) SEAL ALL JOINTS AND ELBOW GORES
5) WHERE IS THE CONDENSATE DRAIN ?
6) ITEMS TO NUMEROUS TO LIST
7) MECHANICAL CONTRACTOR TO BE ON SITE AT NEXT INSPECTION
3) PROVIDE INSTALL