Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T11CM00103
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/09/2011 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
08/04/2011 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* BACKFLOW CONTS REQUESTED ON 6/16, 6/30,7/29 AND 8/1. ELECTRICAL CONNECTION NOTES ON 6/22 FOR RELOCATED & REPLACED WATER HEATER PATCH HOLE IN PIPE WALL ABOVE PRODUCE COMPLETE OVERHEAD PIPING CORRECTIONS |
|
08/03/2011 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
08/02/2011 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CAP OR REMOVE HB AT OLD ? CONNECTION 2) PROVIDE A RIGID TERMINATION WITH A 1" AIR GAP AT DRAIN 3) SECURE ALL TUBING AT RO 4) INSTALL BACKFLOW PROTECTION ON MISTING SYSTEM AS NOTED ON PLAN 5) ALL BACKFLOW ASSEMBLIES REQUIRE A CERTIFICATION TEST AT TIME OF INSTALLATION AND EACH YEAR THEREAFTER 6) SUPPORT PEX OVER HEAD WITH APPROVED SUPPORTS 7) TRAFFIC RATED CLEANOUT COVERS OR CONCRETE |
|
07/29/2011 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
07/29/2011 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* 1) PREPARE FOR AND SCHEDULE ABOVE CEILING INSPECTIONS 2) COMPLETE ? PIPING AND CONNECTIONS WITH BACKFLOW PREVENTIONS FOR MISTING SYSTEM 3) RED LINE ALL CHANGES MADE ON APPROVED PLANS 4) BEVERAGE EQUIPMENT DRAINS AND WATER SUPPLY REQUIRE SUPPORTS AND AIR GAPS 5) ID ALL BACKFLOW ASSEMBLIES, PROVIDE CERTS FOR ALL NEW BACKFLOW ASSEMBLIES 6) TRAP AND TRAP ARM SHALL BE THE SAME SIZE, PROVIDE A FACTORY 'P' TRAP AND APPROVED DRAINAGE FITTINGS 7) EACH FIXTURE REQUIRES SEPERATE SOVS, DO NOT LINK FLEXES 8) RELIEF VALVE TERMINATION TO BE VERTICAL 9) PROTECT PLASTIC VTRS-COMPLETE ANY REMAINING ITEMS 10) CLEANOUT COVERS |
|
06/30/2011 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) REMOVE BRANCH TAIL PIECE AT LAV. PROVIDE BACKFLOW CERTS |
|
06/29/2011 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) RP SHALL BE INSTALLED AT MAX 5' ABOVE FLOOR 603.34, CORRECT THEN TEST. YOU MAY USE THE WATER 2) NEW SUPER IS GINO |
|
06/28/2011 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BACKFLOW PREVENTION ASSEMBLIES REQUIRE ACCESS AS PRESCRIBED BY CODE UPC 603.3.4 2) CERTIFICATION TEST PER SEC 603.1 |
|
06/24/2011 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
06/22/2011 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WATER HEATER REQUIRES TANK, VAC RELIEF VALVE, RELIEF VALVE MAY NOT COMBINE WITH PAN DRAIN, BOTH DRAINS REQUIRE READY ACCESS AT TERMINATION POINT 2) CORRECT ELECTRICAL 3) TD SIZE CORR OK |
|
06/16/2011 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) COMPLETTE WORK IN TOILET ROOMS AND ABOVE 2) NOTE: BACKFLOW PREVENTION ASSEMBLY REQUIRES A CERT TEST. (TOILET ROOMS) 3) LISTED CLEANOUT PLUGS TO ? SCREWS FROM COVER |
|
05/25/2011 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) A FINAL INSPECTION OF THE TOILET ROOMS IS REQUIRED PRIOR TO USE 2) CORRECT LEAKS AND PROVIDE ACCESS |