Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T11CM00077
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Not ready for Inspection
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/04/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
03/04/2011 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
03/02/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
02/28/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
02/02/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. PLANS CALL FOR MINIMUM 3/4" CONDUIT - NEED LETTER AUTHORIZING 1/2" & M/C CABLE OK WALLS SUBJECT TO RECEIVING LETTER |
|
01/31/2011 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WHERE ARE FLOOR BOXES ? 2) IN SET UP ROOM OR OUTLETS AND SPECIAL OUTLETS IN FLOOR OR ON CEILING ? MISSING 3) NO WORK PROGRESS FROM LAST INSPECTION-A REFEE MAY BE ASSESED |
|
01/28/2011 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROTECT M/C CABLE INSIDE CHANNEL OF STUDS 2) M/C CABLE TO BE SUPPORTED PER 300.11 3) PROTECT M/C AT SHALLOW STUDS/BLOCKING 4) TIGHTEN LOOSE FITTINGS 5) FILL UNUSED OPENINGS IN BOXES 6) VERIFY DERATING OF CONDUCTOR 310.15 7) SUPPORT BOXES AND CONDUITS PER CODES 8) VERIFY BOX FILL 9) VDV CABLING IN WALLS AND ABOVE CEILING TO BE PER 725.3 + 24, 800.3 + 24 AND 300.11 10) NO ELECTRICAL PLANS ON SITE |