Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/29/2011 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 05/11/2011 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PVC IS NOT UV RATED 2) PAINT ALL EXPOSED PVC WITH LATEX PAINT 3) PROVIDE A ROOF JACK AT PVC PENETRATION THRU ROOF 4) THE RECEPT ON THE ROOF MUST BE GFI PROTECTED 5) REMOVE THE NEUTRAL WIRES FROM THER 240V HEAT STRIP IN DISCONNECT 6) PROVIDE THE REQUIRED STRUCTURAL DRAWING FOR NEW A/C ON ROOF |
|
| 03/25/2011 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) REMOVE NEUTRAL WIRES CONNECTED TO THE 240 VOLT HEAT STRIP 2) PERMANENTLY I.D. BOTH DISCONNECTS (A/C HEATSTRIP) 3) MARK UNIT DATA PLATE WITH THE PROPER HEAT STRIP INSTALLED AND FUSE ACCORDINGLY 4) CONDENSATE STILL NOT TERMINATED CORRECTLY AND NOT PAINTED 5) PROVIDE THE GFI SERVICE RECEPT IN AIR OUTDOOR BOX WITH A BUBBLE TYPE COVER 6) PROVIDE THE REQUIRED STRUCTURAL DRAWING 7) ALL DUCTING ATTIC TO BE INSULATED WITH MINIMUM R89 |
|
| 02/11/2011 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SUPPORT CONDENSATE DRAIN EVERY 4' AND TERMINATE WITHIN 6" OF THE GROUND 2) PAINT EXPOSED PVC WITH LATEX PAINT, USE PURPLE PRIMER ON ALL FITTINGS PRIOR TO GLUE 3) PROVIDE THE REQUIRED DRAWING FOR NEW A/C ON ROOF 4) IMPROPER WIRING METHODS AT DISCONNECT, 2 WIRES CONNECTED. DO NOT RUN LOW VOLTAGE WIRE IN CONDUIT WITH HIGH VOLTAGE. PROVIDE A BUSHING IN DISCONNECT, 2 WIRES CONNECTED TO 1 LONG, NOT ALLOWED, NO WHITE WIRE ALLOWED 5) MARK UNIT DATA PLATE WITH PROPER HEAT STRIP, PROVIDE A SEPERATE CIRCUIT IF THERE IS A HEAT STRIP 6) PROVIDE THE REQUIRED GFI SERVICE RECEPT ON ROOF 7) PROVIDE MINIMUM R8 DUCTING IN ATTIC 8) SEAL ABANDONED FLUE VENT WITH METAL, NOT TAPE |